Goodrive350 series high-performance multifunction VFD
Function parameter list
-212-
Function
code
Name
Description
Default
value
Modify
protection is performed after motor overload lasts
for 12 minutes; when M=180%, protection is
performed after motor overload lasts for 5 minutes;
when M=200%, protection is performed after
motor overload la
sts for 60 seconds; and when M≥
400%, protection is performed immediately.
Setting range: 20.0%
–120.0%
P12.28
Power display
calibration
coefficient of
motor 2
0.00
–3.00
1.00
○
P12.29
Parameter
display of motor 2
0: Display based on the motor type; under this
mode, only parameters related to current motor
type will be displayed.
1: Display all; under this mode, all the parameters
will be displayed.
0
○
P12.30
System inertia of
motor 2
0
–30.000kgm
2
0.000
kgm
2
○
P12.31
–
P12.32
Reserved
/
/
/
P13
––
Control parameters of synchronous motor
Function
code
Name
Description
Default
value
Modify
P13.00
Reduction rate of
the pull-in current
of synchronous
motor
This parameter is used to set the reduction rate of
the input reactive current. When the active current
of the synchronous motor increases to some
extent, the input reactive current can be reduced to
improve the power factor of the motor.
Setting range: 0.0%
–100.0% (of the motor rated
80.0%
○
1
5
12
60
116%
200%
Time (min)
Current overload
multiple
150%
180%