![INVT GD350-004G-4 Скачать руководство пользователя страница 203](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703203.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-194-
Function
code
Name
Description
Default
value
Modify
channel of process PID.
0: Set by P09.01
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10: EtherCAT/PROFINET/EtherNet IP
communication
11: Programmable card
12: Reserved
The set target of process PID is a relative value,
for which 100% equals 100% of the feedback
signal of the controlled system.
The system always calculates a relative value (0
–
100.0%).
P09.01 PID digital setting
This parameter is mandatory when P09.00 is set to
0. The reference value of this parameter is the
feedback of the system.
Setting range: -100.0%
–100.0%
0.0%
○
P09.02
PID feedback
source
This parameter is used to select PID feedback
channel.
0: AI1
1: AI2
2: AI3
3: High-speed pulse HDIA
4: Modbus/Modbus TCP communication
5: PROFIBUS/CANopen/DeviceNet
communication
6: Ethernet communication
7: High-speed pulse HDIB
8: EtherCAT/PROFINET/EtherNet IP
communication
9: Programmable expansion card
0
○