Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-83-
Function
code
Name
Description
Default
value
P08.06
Running frequency of jog
0.00Hz
–P00.03 (Max. output frequency)
5.00Hz
P08.07
Acceleration time at jogging 0.0
–3600.0s
Depends
on model
P08.08
Deceleration time at jogging 0.0
–3600.0s
Depends
on model
P08.00
Acceleration time 2
0.0
–3600.0s
Depends
on model
P08.01
Declaration time 2
0.0
–3600.0s
Depends
on model
P08.02
Acceleration time 3
0.0
–3600.0s
Depends
on model
P08.03
Declaration time 3
0.0
–3600.0s
Depends
on model
P08.04
Acceleration time 4
0.0
–3600.0s
Depends
on model
P08.05
Declaration time 4
0.0
–3600.0s
Depends
on model
P08.19
Switching frequency of
acceleration/deceleration
time
0.00
–P00.03 (Max. output frequency)
0.00Hz: No switch over
If the running frequency is larger than
P08.19, switch to acceleration
/deceleration time 2
0
P08.21
Reference frequency of
acceleration/deceleration
time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight-line
acceleration/deceleration only
0
P08.28
Automatic fault reset times
0
–10
0
P08.29
Automatic fault reset time
interval
0.1
–3600.0s
1.0s
5.5.8 Frequency setup
The VFD supports multiple kinds of frequency reference modes, which can be categorized into two
types: main reference channel and auxiliary reference channel.
There are two main reference channels, namely A frequency reference channel and B frequency
reference channel. These two channels support simple arithmetical operation between each other,
and they can be switched dynamically by setting multi-function terminals.
There is one input mode for auxiliary reference channel, namely terminal UP/DOWN switch input. By
setting function codes, you can enable the corresponding reference mode and the impact made on