Goodrive350 series high-performance multifunction VFD
Function parameter list
-141-
Function
code
Name
Description
Default
value
Modify
eliminate the impact on the output voltage of VFD
when bus voltage fluctuates.
P00.17
Reserved
P00.18
Function
parameter
restoration
0: No operation
1: Restore default values (excluding motor
parameters)
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test mode)
6: Restore default values (including motor
parameters)
Note:
After the selected operation is performed,
this parameter is automatically restored to 0.
Restoring the default values may delete the user
password. Exercise caution when using this
function. The option 5 can be used only for factory
testing.
0
◎
P01
––
Start/stop control
Function
code
Name
Description
Default
value
Modify
P01.00
Running mode of
start
0: Direct start
1: Start after DC brake
2: Start after speed tracking
0
◎
P01.01
Starting
frequency of
direct start
Starting frequency of direct startup is the initial
frequency when the VFD starts. See P01.02 (hold
time of starting frequency) for details.
Setting range: 0.00
–50.00Hz
0.50Hz
◎
P01.02
Hold time of
starting
frequency
Output frequency
fmax
t1
t
f1 set by P01.01
f1
t1 set by P01.02
A proper starting frequency can increase the
torque during startup. Within the hold time of
starting frequency, the output frequency of VFD is
the starting frequency, and then it runs from the
starting frequency to the target frequency, if the
target frequency (frequency command) is below
0.0s
◎