Goodrive350 series high-performance multifunction VFD
Function parameter list
-138-
Function
code
Name
Description
Default
value
Modify
When the set frequency is higher than the upper
limit, the VFD runs at the upper limit frequency.
Setting range: P00.05
–P00.03 (Max. output
frequency)
P00.05
Lower limit of
running
frequency
The lower limit of running frequency is the lower
limit value of VFD output frequency.
When the set frequency is lower than the lower
limit, the VFD runs at the lower limit frequency.
Note: Max. output frequency
≥ upper limit
frequency
≥ lower limit frequency.
Setting range: 0.00Hz
–P00.04 (upper limit of
running frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
0: Keypad
1: AI1
2: AI2
3: AI3
4: High speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus/Modbus TCP communication
9: PROFIBUS/CANopen/DeviceNet
communication
10: Ethernet communication
11: High speed pulse HDIB
12: Pulse train AB
13: EtherCAT/PROFINET/EtherNet IP
communication
14: Programmable card
15: Reserved
0
○
P00.07
B frequency
command
selection
15
○
P00.08
Reference object
of B frequency
command
0: Max. output frequency
1: A frequency command
0
○
P00.09
Combination
mode of setting
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max. (A, B)
5: Min. (A, B)
0
○