Goodrive350 series high-performance multifunction VFD
Function parameter list
-143-
Function
code
Name
Description
Default
value
Modify
section of
acceleration S
curve
acceleration range and acceleration and
deceleration time.
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06
t2=P01.07
t3=P01.27
t4=P01.28
Setting range: 0.0
–50.0s
P01.07
Time of ending
section of
acceleration S
curve
0.1s
◎
P01.08
Stop mode
0: Decelerate to stop; after stop command is valid,
the VFD lowers output frequency based on the
deceleration mode and the defined deceleration
time, after the frequency drops to the stop speed
(P01.15), the VFD stops.
1: Coast to stop; after stop command is valid, the
VFD stops output immediately, and the load coasts
to stop as per mechanical inertia.
0
○
P01.09
Starting
frequency of DC
braking after stop
Starting frequency of DC braking after stop; during
decelerating to stop, when this frequency is
reached, DC braking will be performed after stop.
Demagnetization time (waiting time of DC braking
after stop): Before the DC brake, the VFD will
block output, and after the demagnetization time
elapses, DC braking will start. This function is used
to prevent overcurrent fault caused by DC braking
during high speed.
DC braking current after stop: it means the DC
braking force applied, the larger the current, the
stronger the DC braking effect.
P01.04
ACC
P01.30
P01.23
Constant speed
In running
DEC
P01.10
P01.31
P01.12
P01.09
Time t
Setting range of P01.09: 0.00Hz
–P00.03 (Max.
output frequency)
Setting range of P01.10: 0.00
–30.00s
Setting range of P01.11: 0.0
–100.0% (of the rated
0.00Hz
○
P01.10
Waiting time of
DC braking after
stop
0.00s
○
P01.11
DC braking
current of stop
0.0%
○
P01.12
DC braking time
of stop
0.00s
○