Goodrive350 series high-performance multifunction VFD
Optional peripheral accessories
-410-
VFD model
Input filter
Output filter
GD350-250G-6
GD350-280G-6
GD350-315G-6
FLT-P06400H-B
FLT-L06400H-B
GD350-355G-6
GD350-400G-6
FLT-P061000H-B
FLT-L061000H
GD350-450G-6
GD350-500G-6
GD350-560G-6
GD350-630G-6
Refer to the preceding table for the filter model selection for a paralel VFD system.
Note:
The input EMI meets the C2 requirements after an input filter is configured.
The preceding table describes external accessories. You need to specify whether external or
built-in accessories are needed in your purchase order.
D.8 Braking system
D.8.1 Braking component selection
When the VFD driving a high-inertia load decelerates or needs to decelerate abruptly, the motor runs
in the power generation state and transmits the load-carrying energy to the DC circuit of the VFD,
causing the bus voltage of the VFD to rise. If the bus voltage exceeds a specific value, the VFD
reports an overvoltage fault. To prevent this from happening, you need to configure braking
components.
The design, installation, commissioning, and operation of the device must be
performed by trained and qualified professionals.
Follow all the "Warning" instructions during the operation. Otherwise, major
physical injuries or property loss may be caused.
Only qualified electricians are allowed to perform the wiring. Otherwise,
damage to the VFD or braking components may be caused.
Read the braking resistor or unit instructions carefully before connecting
them to the VFD.
Connect braking resistors only to the terminals PB and (+), and braking units
only to the terminals (+) and (-). Do not connect them to other terminals.
Otherwise, damage to the braking circuit and VFD and fire may be caused.
Connect the braking components to the VFD according to the wiring diagram.
If the wiring is not properly performed, damage to the VFD or other devices
may be caused.
The 380V 37kW and lower VFD models are equipped with built-in braking units, and the 380V 45kW
and higher VFD models need to be configured with external braking units. The 380V 45kW
–110kW