IDS X-Series Training v2.7 | Hardware
9
Zones
17 to 24
Zones
25 to 32
Zones
33 to 40
Zones
41 to 48
Zones
49 to 56
Zones
57 to 64
7.
Onboard Expander Connection
The number of zones on the X64 and X16 alarm panels can be expanded via zone expanders. Zones 9 to
16 are added by plugging the onboard expander (or plug-in expander) onto the PCB via this connector.
Not available on the X8s.
8 pin connect Standoff mounting hole
8.
Keypad Bus
All devices connected to the bus should be connected in a daisy chain formation (one after each other) for
the best results, though the X-Series Panel does not need to be in the beginning or end of the daisy chain.
Note: All X-Series keypad bus devices must be powered from the X-Series panel unless an IDS RS485 Bus
Isolator is used, as described in point 8.6.
8.1.
IDS X64 – Wired 8 Zone Expander Module
NOTE: Zone 9 - 16 are reserved for the onboard plug-in expander and cannot be allocated to the
wired bus expander zones, even if the onboard expander is not used.
PGM – 12V output
Zones – End of Line Supervised
Tamper – Connects directly to a tamper
switch
12V – Connect to keypad bus
D+ D- – Connect to keypad bus
Dipswitch – ID the expander using
binary as shown below
19