Chapter 5 function code
table
- 46
-
P06.28
DI4 ineffective delay time
0.000s
~
30.000s
0.000s
☆
P06.29
Two wire/3wire operation
control
0
:
2-wire mode (FWD+REV)1
1
:
2-wire mode RUN+DIRECTION)2
2
:
3-wire 1(FWD+REV+ENABLE)
3
:
3-wire 2 RUN +FWD/REV+ENABLE
0
★
K1
DI1 Forward
K1
DI1 operation
Run (FWD)
function
K2
DI2 Reverse
K2
DI2 operation
RUN (REV)
direction
COM
COM
Figure1
:
Two-line mode
1
Figure 2
:
Two-line mode
2
SB2
DI1 forward
SB2
DI1 forward
command
command
SB1
DI3 operation
SB1
DI3 stop
command
command
SB3
DI2 reverse
K
DI2 operation
command
direction
COM
COM
Figure 3
:
Three-line mode
1
Figure 4
:
Three
-line mode
2
Two-line mode 1:
K1 is closed, the drive is running forward, K2 closed reverse operation, K1, K2 at the same time closed or
disconnected, the inverter stops running.
Two-line mode 2:
In K1 closed state, K2 disconnect the inverter forward, K2 closed inverter reverse; K1 off the inverter to stop
running.
Three-line mode 1:
DI3 is set to three-wire control function. When the SB1 button is closed, press the SB2 button. The inverter is
forward running. Press the SB3 button to invert the inverter. When the SB1 button is off, the inverter will stop.
During normal start-up and running, it is necessary to keep the SB1 button closed, and the commands of SB2
and SB3 buttons take effect during the closing operation. The running status of the inverter takes the last key
action of the three buttons as the standard.
Three-line mode 2:
DI3 is set to three-wire control function. When the SB1 button is closed, press the SB2 button to run the inverter,
K to switch the inverter forward, K to close the inverter and SB1 to turn off the inverter. During normal start-up
and operation, it is necessary to keep the SB1 button closed and the command of the SB2 button effective during
the closing operation.
P06.30
Digital input
termimal filtering time
0.000
~
0.100s
0.010s
☆
P06.31
Terminal protection
function
0
:
no protection
When command is terminal ,power on and
terminal effective,inverter will run
1
:
protection
0
★