Chapter3 Product appearance and wiring
-
19-
C
:
NPN mode uses ex24V power supply
D
:
PNP mode uses ex24V power supply
3-13 Switching Digital input terminal wiring diagram
Note
:
When using an external power supply, the shorting tab b24V and PLC must be removed, otherwise the
product will be damaged!
When using an external power supply, connect the negative terminal of the external power supply to COM when
using HDI, otherwise HDI is invalid!
Switch output terminal instructions
The multi-function output terminals DO1 and HDO can be powered by the in24V power supply of the inverter
or an external power supply. The wiring diagram is as follows:
A
、
Use internal power supply
B
、
Use external power supply
3-14 Switching digital output terminal wiring diagram
Note
:
The multi-function terminal output is an open collector output with a maximum allowable current of 50mA. When
using the internal power supply, if the inductive load is driven, an absorption circuit such as an RC snubber circuit or
a freewheeling diode should be installed. When adding a freewheeling diode, be sure to confirm the polarity of the
diode, otherwise the product will be damaged. For external power supply, connect the negative terminal of the