ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 30
-
Functio
n code
Parameter name
Description
Default
Property
01Group frequency source selction
P01.00
Main frequency source
selection (A)
0
:
Digital setting
1
:
AI1
2
:
AI2
3
:
AI3(reserved)
4
:
AI4
(
reserved
)
5
:
HDI
6
:
multi-step speed
7
:
communication
8
:
PID
9
:
Internal PLC
Notice:DI terminal function code 26-32 superior
than this function code
0
★
P01.01
Auxiliary frequency
source selection (B)
Same as P01.00
Notice:DI terminal function code 33 superior
than this function code
0
★
P01.02
Reference option for
auxiliary frequency
source
0
:
Relative to Maximum frequency
1
:
Relative to main frequency
0
★
P01.03
Auxiliary frequency gains
0.0
~
300.0
100.0%
☆
P01.04
Frequency source
selection
0
:
main frequency source A
1
:
auxiliary frequency source B
2
:
Main and auxiliary arithmetic results
3
:
Switchover between main and auxiliary
frequency
4
:
switchover between main frequency source
A and A+B Arithmetic results
5
:
Switchover between B and (A+B)
(
*
)
DI function code 25 effective to
corresponding terminal ,frequency will adopt
the latter
0
★
P01.05
Main and Auxiliary
arithmetic
0
:
A+B
1
:
A-B
2
:
The bigger of main A and Auxliary B
3
:
The smaller of Main A and Auxiliary B
0
★
P01.06
Maximum frequency
10.00
~
600.00Hz
50.00Hz
★
P01.07
Upper limit frequency
control
0
:
digital setting (set through P01.08)
1
:
AI1
2
:
AI2
3
:
Reserved
4
:
Reserved
5
:
Pulse setting HDI
6
:
Reserved
7
:
Communication setting
0
★