Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
39-
Function
code
Parameter name
Description
Default
Property
P03.14
S-curve
Deceleration
Arrival time
SAME AS P03.11
0.50s
☆
P03.15
Accel and
Deceltime
frequency
benchmark
0
:
maximum frequency
1
:
Motor rated frequency
0
★
P03.16
Accel and Decel
time unit selection
0
:
1s
1
:
0.1s
2
:
0.01s
2
★
P03.17
Quickstop
deceleration time
0.01
~
65000s
5.00s
☆
P03.18
Switchingfrequency
1 in acceleration
time
0.00Hz
~
maximum frequency(P01.06)
0.00Hz
☆
P03.19
Switchingfrequency
1 in deceleration
time
0.00Hz
~
maximum frequency(P01.06)
0.00Hz
☆
P03.20
Forward/reverse
Dead block time
0.00s
~
30.00s Waiting time for zero speed during forward and
reverse switchover
0.00s
★
04 Group Analog and Pulse input
P04.00
Minimum input
pulse frequency
0.00kHz
~
50.00kHz
Corresponding setting
P04.03
P04.02
P04.00
P04.01
HDI input frequency
1.00kHz
☆
P04.01
Maximum input
pulse frequency
0.00kHz
~
50.00kHz
30.00kHz
☆
P04.02
Setting
Corresponding to
Minimum input
-100.0%
~
100.0%
0.0%
☆
P04.03
Setting
Corresponding to
maximum input
-100.0%
~
100.0%
100.0%
☆
P04.04
Pulse input filter
time
0.000s
~
10.000s
0.050s
☆
r04.05
Pluse input
frequency
0.00kHz
~
50.00kHz(it is used to check HDI pulse input
frequency)
-
●
r04.06
HDI equivalent
value
-100.0%
~
100.0%(it is used to View the output of the HDI
mapping curve)
-
●
P04.07
AI 1 Curve setting
Unit’s
:
AI curve selection
0
:
curve A
1
:
curve B
2
:
Curve C
3
:
Curve D
00
★