Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
77-
when valid
2
:
automatic switchover based on deviation
The absolute value of PID command and
feedback deviation is less than P40.24, using
KP1, TI1, TD1; the absolute value of
deviation is greater than P40.25, using KP2,
TI2, TD2 parameters; the absolute value of
deviation is between P40.24~P40.25, The
two sets of parameters are linearly
transitioned.
P40.24
PID parameter
switchover
devation 1
0.0%
~
P40-25
20.0%
☆
P40.25
PID parameter
switchover
devation 2
P40-24
~
100.0%
80.0%
☆
P40.26
PID integral
separation
threshold
0.0%
~
100.0%
100.0%
☆
P40.27
PID initial value
0.0%
~
100.0%
0.0%
☆
P40.28
PID intial value
holding time
0.00
~
650.00s
0.00s
☆
This function is only valid when P40.39 = 0 which is not calculated. The PID output is reset after the inverter stops. If
P40.28
≠ 0, when the inverter runs, the PID output is equal to the initial value of PID and keeps the time of P40.28.
.
P40.29
PID deviation
limit
0.0%
~
100.0%
0.0%
☆
P40.30
PID differential
limit
0.00%
~
100.00%
1.00%
☆
P40.33
PID feedback
filter time
0.000
~
30.000s
0.010s
☆
P40.34
PID output filter
time
0.000
~
30.000s
0.010s
☆
P40.35
Detection value
of PID feedback
loss ( lower limit)
0.0%(no detection )
~
100.0%
0.0%
☆
P40.36
Detection time of
PID feedback
loss
0.000s
~
30.000s
0.000s
☆
P40.37
Detection value
of PID feedback
loss( upper limit)
0.0%
~
100.0%(no detection)
100.0%
☆
P40.38
Upper Detection
time of PID
feedback loss
0.000s
~
30.000s
0.000s
☆