Chapter 5 function code
table
- 72
-
Bit6
~
7:current running
mode:0-speed;1-torque;2-position
r27.14
Accumulated
power on time
Unit:hour
-
●
r27.15
Accumulated
running time
Unit:hour
-
●
r27.18
Heat sink
temperature
Unit:0.1
℃
-
●
r27.19
Main frequency
Unit:0.01Hz
-
●
r27.20
Auxiliary
frequency
unit:0.01Hz
-
●
r27.21
Up Down offset
frequency
unit:0.01Hz
-
●
30 Group Modbus communication parameter
P30.00
Communication
type
0:Modbus;
1
~
2:can Open/profibus and reserved
0
★
P30.01
Drive Address
1
~
247
Different slaves on the same network
should set different local addresses;
0 is the broadcast address, all slave
inverters can be identified
1
★
P30.02
Modbus baud rate
0:1200 bps;
1:2400 bps
2:4800 bps;
3:9600 bps
4:19200 bps; 5:38400 bps
6:57600 bps; 7:115200 bps
3
★
P30.03
Modbus data
format
0: 1-8-N-1
(1 start bit +8 data bits +1 stop bits )
1: 1-8-E-1
(1start bit +8 data bits +1 even 1
stop bit)
2: 1-8-0-1
(1 star bit+8 data bits +1odd 1
stop bits)
3: 1-8-N-2
(1 star bit+8 data bits+2 stop bits)
4: 1-8-E-2
(1 star bits+8 data bit+1 even 2
stop bits)
5: 1-8-0-2
(1 start bit +8 data bits+1 odd 2
stop bits)
0
★
P30.04
Modbus response
delay
1
~
20msThe delay time of the local to
answer the master
2ms
★
P30.05
Modbus overtime
0.0s(disabled)
~
60.0s(works for
master-slave system) When this function
code effective,if slave do not receive data
0.0s
★