ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 28
-
Function
code
Parameter name
Description
Default Property
00 Group Basic Function
P00.00
User password
0 ~ 65535
No user password status (P00.01 = 1
after power-on):
Entering the same non-zero value twice in
succession sets a user password and enters
lockout.
Password lock state:
Enter the password to enter the unlock state.
Unlocked state:
Enter the original password to enter the lock
state; enter the same value twice in a row to
change the password (clear the password if
you enter 0 twice in a row).
0
☆
P00.01
Access authority
0
:
END USER
Some parameter are not authorized to check
when user password in locked state 1
:
Standard
ALL Parameter can be checked
1
★
P00.02
Parameter copy and
backup
0
:
No action
11
:
save all parameter to EEPROM backup
space
12
:
Restore all parameter from EEPROM
backup space
13
:
Parameter upload to LCD ICON500
(excluded for motor parameter and auto
tune related parameter)
14
:
Parameter upload to LCD ICON500
(All parameter except for factory data)
0
★
P00.03
RESET
0
:
NO ACTION
11
:
Restore default parameter except for motor
parameter and auto-tune related parameter
and factory parameter
12:Restore default to factory parameter
13
:
Clear tripping record
0
★
P00.04
Motor Control mode
0
:
VF
1
:
SVC(sensorless vector control)
Open loop vector and torque
controlwithout encoder feedback
2
:
VC Vector control with sensor
Close loop vec tor and torque control
supporting encoder feedback in high
precision or torque control application
0
★