ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 34
-
Functio
n code
Parameter name
Description
Default
Property
P01.44
Textile frequency
0.0%
~
100% relative to center of textile
frequency P01.43 = 0 Textile frequency Aw =
P01.44 * center frequency
P01.43 = 1: Textile frequency Aw = P01.44 *
max frequency
0.0%
☆
P01.45
Jump frequency
0.0%
~
50.0% relative to textile frequency
0.0%
☆
P01.46
Textile period
0.1s
~
3000.0s
10.0s
☆
P01.47
Triangle wave rising time
coeffcient
0.1%
~
100.0% relative to textile period
50.0%
☆
This function is mostly used in textile and chemical industry and some application such as traversing and winding so
it is used for balancing the workload allocation when multiple motors are used to drive the same load. The output
frequency of the frequency inverters decreases as the load increases. You can reduce the workload of the motor
under load by decreasing the output frequency for this motor, implementing workload balancing among multiple
motors.
P01.44 or P01.46=0,This function disable
Output frequency
Frequency swing range:AW-set the frequency(choose
Frequency
P01.43)*P01.44 Kick-hop frequency:jw-aw*P01.45
swing limit
+A
Jw
w
Frequency
swing center
Jw
Frequency swing
-Aw
lower limit
Triangle wave rise time:
P01.47*frequency swing
cycle
Start acceleration
Frequency swing
Deceleration stop
Running
cycle (P01.46)
command