ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 44
-
06 Group Multi-function Digital input
r06.00
DI port status
Bit0
~
Bit6 Correspond to DO1
~
DO7
Bit12
~
Bit15 Correspond to VDI1
~
VDI4
-
●
P06.01
DI1 Numeric input function
0
:
no function
1
:
run terminal
2
:
reverse/Forward and reverse switchover
3
:
three wire control
4
:
forward jog command
5
:
reverse jog command
6
:
Terminal UP
7
:
Terminal DOWN
8
:
Clear up UP/DOWN offset
9
:
coast to stop/free stop
10
:
fault reset
11
:
Reverse forbidden
12
:
Switching run command to Keypad
13
:
Switching run command to Communication
14
:
fast stop
15
:
external stop
16
:
Switch between motor 1 and motor 2
17
:
Pause operatoin
18
:
DC braking
19
:
Switch between torque and speed Control
20
:
torque control diabled
21
:
Multi-step speed terminal 1
22
:
Multi-step speed terminal 2
23
:
Multi-step speed terminal 3
24
:
Multi-step speed terminal 4
25
:
frequency source switchover
26
:
Switch main frequency source to Numeric
frequency setting
27
:
Switch main frequency source to AI1
28
:
Switch main frequency source to AI2
29
:
Switch main frequency source to AI3
30
:
Switch main frequency source to AI4
31
:
Switch main frequency source to
high-frequency pulse input
32
:
Switch main frequency source to
communication setting
33
:
Switch auxiliary frequency source to numeric
frequency setting
34
:
Accel and Decel time terminal 1
35
:
Accel and Decel time termina2
1
★
P06.02
DI2 Numeric input function
2
★
P06.03
DI3 Numeric input function
4
★
P06.04
DI4 Numeric input function
10
★
P06.05
DI5(HDI) Numeric input
function
0
★
P06.06
DI6 Numeric input function
(
option card
)
0
★
P06.07
DI7 Numeric input function
(
option card
)
0
★
P06.13
VDI1 Numeric input
function
(
option card
)
0
★