12 Group Motor 1 VF control parameter
P12.00
VF curve
0
:
linear VF
1
:
Multi-point VF
2
:
VF to the 1.3
3
:
1.7 power
4
:
2.0 power
5
:
VFcomplete separation
6
:
VF Half separation
0
★
When the VF curve is straight line and power curve, the frequency-voltage curve is as follows:
Output
Voltage
2.0
1.7powepower
Motor rated
r
Voltage
1.3
power
Straight line V/F
Output
frequenc
0
Motor rated
y
frequency
Figure 1
:
Straight line VF and 1.3
、
1.7
、
2.0 power VF
mult-i stage line type VF curve
:
Output
voltage
Motor rated
voltage
V3
V2
V1
Output
V0
frequen
cy
0
F F
F
F
Motor rated
0
1
2
3
frequency
Figure 2
:
mult-i stage line type VF curve
VF full separation
The output voltage and output frequency are completely independent. The output frequency is determined by the
frequency source. The output voltage is determined by P12.20. Suitable for applications such as variable
frequency power or torque motors.
VF sem-i isolated
At this point the ratio of output voltage and output frequency given by the voltage source, the formula is as
follows:
:
P12.01
Multi-point VF Frequency
1(F0)
0.00Hz
~
multi-point VF curve F1(P12.03)
0.00Hz
☆
P12.02
Multi-point VF Voltage 0(V0)
0.0%
~
100.0%
0.0%
☆
P12.03
Multi-point VF Frequency
1(F1)
multi-point VF curve F0(P12.01)
~
multi-point
VF curve F2(P12.05)
50.00Hz
☆
P12.04
Multi-point VF Voltage 1(V1)
0.0%
~
100.0%
100.0%
☆
P12.05
Multi-point VF Frequency
multi-point VF curve F1(P12.03)
~
multi-point
50.00Hz
☆