Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
35-
Function
code
Parameter name
Description
Default Property
02 Group Start and stop Control
P02.00
Starting mode
0
:
Direct start
Inverter will start from P02.01,After P02.02,It
will go to setting frequency as per S curve
1
:
Speed tracking/Searching
Inverter will do search for motor speed and
recognize and accelerate and decelerate to
setting frequency.See Parameter
P02.16-P02.19
0
★
P02.01
Startup frequency
0.00Hz
~
10.00Hz
0.00Hz
★
P02.02
Startup frequency
holding time
0.000s
~
10.000s
0.000s
★
P02.03
Quick-response
excitation
0
:
Disable
1
:
Enable
Set 1= enable it will automatically calculate
pre-exciation current P02.04 and pre-excitaton
time ,after finishing calculation,this parameter
will reset to 0
0
★
P02.04
Pre-excitation current
0%
~
200% motor rated current
Depend
★
P02.05
Pre-excitation time
0.00s
~
10.00s
Pre-excitation enable Asynchronous motor for
magnetic field for higher starting torque
Depend
★
P02.06
DC brake current at
start-up
0
~
100% motor rated current
100%
☆
P02.07
DC brake time at
start-up
0.000s
~
30.000s
0.000s
★
P02.08
Stop method
0
:
Ramp to stop
1
:
Free coast to stop
0
☆
P02.09
Startup frequency of DC
brake at stop
0.00Hz
~
50.00Hz
1.00Hz
★
P02.10
DC braking current at
stop
0
~
100% motor rated current(Maximum value
not higher than drive rated current)
100%
☆
P02.11
DC brake time at stop
0.000s
~
30.000s
0.000s
★
P02.12
Magnetic flux brake gain
1.00
~
1.50
Over excitation braking convert some kinetic
energy to motor heating by increasing motor
excitation.value 1 means ineffective: value
higher,better performance but output current
bigger
1.00
★
P02.13
Delaying frequency at
stop
0.00Hz
~
20.00Hz
0.50Hz
★
P02.14
Delaying time at stop
0.000s
~
60.000s
0.000s:no function for delaying time at stop
>0.000s:it is effective,when output frequency
0.000s
★