Chapter 2 Product information
ICON500
high performance vector control frequency inverter user
manual
- 6
-
Undervoltage stall control: control the power consumption of the motor
by adjusting the output frequency to avoid yaw failure
VdcMax Control: Limit the amount of power generated by the motor by
adjusting the output frequency to avoid over-voltage trip;
VdcMin control: Control the power consumption of the motor by
adjusting the output frequency, to avoid jump undervoltage fault
Carrier frequency
1kHz
~
12kHz(Varies depending on the type)
Startup method
Direct start (can be superimposed DC brake); speed tracking start
Stop method
Deceleration stop (can be superimposed DC braking); free to stop
Maincontrol
function
Jog control, droop control, up to 16-speed operation, dangerous speed
avoidance, swing frequency operation, acceleration and deceleration
time switching, VF separation, over excitation braking, process PID
control, sleep and wake-up function, built-in simple PLC logic, virtual
Input and output terminals, built-in delay unit, built-in comparison unit
and logic unit, parameter backup and recovery, perfect fault record,fault
reset, two groups of motor parameters free switching, software swap
output wiring, terminals UP / DOWN
Function
Keypad
LED Digital keyboard and LCD keypad(option)
communication
Standard:
MODBUS communication
Option:Profibus-DP and CAN OPEN
PG card
Incremental Encoder Interface Card (Differential Output and Open
Collector), Rotary transformer Card
Input terminal
Standard:
5 digital input terminals, one of which supports high-speed pulse input
up to 50kHz;
2 analog input terminals, support 0 ~ 10V voltage input or 0 ~ 20mA
current input;
Option card:
4 digital input terminals
2 analog input terminals.support-10V-+10V voltage input
Output terminal
standard:
1 digital output terminal;
1 high-speed pulse output terminal (open collector type), support 0 ~
50kHz square wave signal output;
1 relay output terminal(second relay is an option )
2 analog output terminals, support 0 ~ 20mA current output or 0 ~ 10V
voltage output;
Option card: 4 digital output terminals
Protection
Refer to Chapter 6 "Troubleshooting and Countermeasures" for the protection function
Environment
Installation
location
Indoor, no direct sunlight, dust, corrosive gas, combustible gas, oil
smoke, vapor, drip or salt.
Altitude
0-3000m.inverter will be derated if altitude higher than1000m and
rated output current will reduce by 1% if altitude increase by 100m
Ambient
temperature
-10°C~ +40°C,maximum 50°C (derated if the ambient temperature is
between 40°C and 50°C)Rated output current decrease by 1.5% if
temperature increase by 1°C
Humidity
Less than 95%RH, without condensing
Vibration
Less than 5.9 m/s
2
(0.6 g)
Storage
temperature
-20°C ~ +60°C
Others
Installation
Wall-mounted, floor-controlled cabinet, transmural
Protection level
IP20
cooling method
Forced air cooling