Chapter 5 function code
table
- 66
-
1: fast stop
2: stop as per stop mode
3: continue to run
Hu
ndred’s unit: PG card fault(reserved)
0: coast to stop
1: fast stop
2: stop as per stop mode
3: continue to run
Thousand’s unit: off load fault
0: coast to stop
1: fast stop
2: stop as per stop mode
3: continue to run
P23.24
Fault reset
Define as per bit:
bit0-undervoltage;bit1- inverter overload
bit2-inverter overheat ;bit3-motor overload
bit4-motor overheat;bit5-
user’fault 1
bit6-
user’fault 2; bit7
~
15 reserved
0
☆
P23.25
Fault source for auto reset
Define as per bit:
bit0-overcurrent during
acceleration;bit1-overcurrent during deceleration
bit2-overcurrent during constant speed;bit3-over
voltage during acceleration
bit4-overvoltage during
deceleratoin;bit5-overvoltage during
bit6-inverter undervoltage;bit7-input phase loss
bit8-inverter overload;bit9-inverter overheat
bit10-motor overload;bit11-motor overheat
bit12-
user’fault 1;bit13-user’fault 2
bit14-Reserved;bit15-Reserved
0
☆
P23.26
Fault auto Reset times
0
~
99
0
☆
P23.27
Numberic output Action at
fault reset
0:disabled
1:enabled
0
☆
P23.28
Interval time of fault auto
reset
0.1s
~
300.0s
0.5s
☆
P23.29
Fault auto reset times
clearing time
0.1s
~
3600.0s
10.0s
☆
P23.30
Continuing Running
frequency selection when
trip
0
:
run at current frequency
1
:
run at setted frequency
2
:
run at upper limite frequency
3
:
run at lower limit frequency
4
:
run at abnormal back-up frequency
0
☆
P23.31
Abnormal back-up
frequency
0.0%
~
100.0%(maximum frequency )
5.0%
☆