Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
47-
When command is terminal ,power on and
terminal effective, inverter will not run ,so need
terminal ineffective then effective,then inverter
will run
P06.32
DI terminal on/ready time
0.000s
~
30.000s
1.000s
★
07 Group Multi-function Digital output
r07.00
DO output port status
Define as per bit,
0:ineffective 1:effective
Bit0:DO1 Bit1:D02 Bit2:relay1, Bit 3:relay 2 Bit4:
DO3;Bit5: DO4 Bit6: DO5; Bit7: DO6
Bit8: VDO1;Bit9: VDO2
-
●
P07.01
DO1 Output terminal
function group
0:no function
1:READY
2:RUN
3:Error1
(
stop fault
)
4:Error2
(
same as Error1 except undervoltage
)
5:warning output(fault but in running)
6:swing frequency limit
7:torque limit
8:reverse running
9: upper limit frequency arrival
10:lower limit frequency arrival 1
11: lower limit frequency arrival2
12:FDT1 output frequency detection range
13:FDT2 output frequency detection range
14:setting frequency arrival
15:Desired frequency attained 1 P08.05
16:Desired frequency attained 2P08.07
17:zero speed
(
stop without output
)
18: zero speed
(
stop with output
)
19:zero current status
20:output current exceed limit
21:counter 1 setting value arrival
22:counter 1 setting value arrival
23:Simple PLC cycle finish
24:IGBT temperature arrival
25:Drive overload pre-warning
26: motor overload pre-warning
27: motor overheat pre-warning
28:in off loading
29:Accumulated on power time arrival
30:Accumulated running time arrival
0
☆
P07.02
DO2(HDO) Output
terminal function group
0
☆
P07.03
Relay 2 Output terminal
function group(T1A T1B
T1C)
3
☆
P07.04
Relay 2 Output terminal
function group(T2A T2B
T2C)
0
☆
P07.09
VDO1(virtual DO1) output
Terminal function
0
☆