ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 36
-
Function
code
Parameter name
Description
Default Property
decrease lower than delaying frequency at
stop (P02.13),inverter will block pulse output
after delaying time at stop (P02.14).if run
command comes during delaying time,inverter
will restart.it is useful to some application with
jog function
P02.15
The minimum blocking
time after free stop
0.010s
~
30.000s
Depend
★
P02.16
Speed search mode
Unit’s digit
:
tracking mode
0
:
speed search for maximum output
frequency
1
:
speed search for frequency at stop
2
:
speed search for grid frequency
Ten’s digit
:
direction choosing
0
:
only search at given frequency direction
1
:
search on the other direction when failed for
given frequency tracking
10
★
P02.17
Deceleration time for
speed search
0.1s
~
20.0s
2.0s
★
P02.18
Current for speed search 10%
~
150% motor rated current
40%
★
P02.19
Speed search
compensation factor
0.00
~
10.00
1.00
★