NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
33
Application
Scenario
Name
Technical Specifications
Description
communications cable
Insertion Depth 6 mm, 2 A, Light
blue
Teamwork
control
networking
and the
monitoring
cable to the
host computer
Standard network cable
(optional)
Symmetric twisted-pair cable, 100
ohm, enhanced class five cable,
aluminum foil shield, 0.52 mm, 24
AWG, 8-core, four pairs of
PANTONE 430U, equipped with
plug 14080097
1 PCS (10 m)
Indoor and
outdoor unit
Cord end terminal of indoor
and outdoor unit connection
cable
Common Terminal, Single Cord
End Terminal, Conductor Cross
Section 1.0 mm
2
, 5 A, Tin Plating,
Insertion Depth 12 mm, Red
Delivered with the
accessories
3.1.2.8 (Engineering Procurement) Water Softener
If the water hardness exceeds 100 mg/L (CaCO
3
), install water purification equipment to
reduce scaling and ensure the stable running of the system. The detailed specifications are as
follows:
Table 3-9
Water softener specifications
Item
Specifications
Water flow
0.5 m
3
/h
Water inlet pressure
0.1–0.7 MPa
Water inlet temperature
1–40°C
Water inlet hardness
≤ 800 mg/L
Water outlet hardness
≤ 3 mg/L
Filtration rate
20–25 m/h
Design pressure
≤ 0.6 MPa
Operating pressure
0.2–0.45 MPa
Operating temperature
5–50°C
3.1.3 Deployment Principles
Check cabinets comprehensively and handle problems immediately.
Before installation, check that the environment meets requirements and check whether
reconstruction is needed for routing pipes and cables and constructing ventilation pipes.
Содержание NetCol5000-A021