NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
170
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
gauge is
short-circuited
or the circuit is
faulty.
After the alarm is rectified, click
Manual clear
on the alarm page.
a124
Low
conductivity
Warning
The alarm is
generated.
1.
The inlet water
conductivity is
lower than the
threshold
100μS/cm.
2.
The
conductivity
gauge is
open-circuit or
the circuit is
faulty.
1.
Verify that the water
conductivity meets the
requirement.
2.
Check the conductivity
gauge and the circuit.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a126
Drainage failure Major
The humidifier
is shut down.
1.
The water inlet
solenoid valve
leaks.
2.
The drainage
solenoid valve
is faulty or
blocked.
3.
The drainpipe is
blocked.
1.
Verify that the inlet water
valve works properly.
Wash or replace the valve
if necessary.
2.
Verify that cables to the
drainage solenoid valve are
properly connected. Wash
or replace the valve if
necessary.
3.
Verify that the drainpipe
can drain water smoothly.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a127
Cylinder
overcurrent
Major
The alarm is
generated.
1.
The electrodes
in the
humidifier
cylinder or the
power cables
are
short-circuited.
2.
The water inlet
solenoid valve
leaks.
3.
The inlet water
conductivity
exceeds the
upper threshold.
4.
The current
transformer
circuit is faulty.
5.
The drainage
solenoid valve
is faulty or
1.
Verify that electrodes are
normal, not burnt or
short-circuited, and the
power cable is not
short-circuited. Wash or
replace cylinder.
2.
Verify that cables to the
water inlet solenoid valve
are properly connected.
Wash or replace the valve
if necessary.
3.
Verify that the inlet water
conductivity is within the
threshold.
4.
Verify that the current
transformer circuit is
normal.
5.
Verify that cables to the
drainage solenoid valve are
properly connected. Wash
Содержание NetCol5000-A021