NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
98
Parameter Description
Configuration
Principle
Default Value
group no.
group, which is the same
for all the devices in the
group.
number.
Teamwork
unit address
Only one device in each
group can be set to
1
.
Other device addresses
should be different from
each other.
Set the assigned unit
address.
NA
Teamwork
function
Disable or enable the
teamwork function. If the
teamwork function is
disabled, this device is
operating according to its
own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
Set this parameter based
on the onsite device heat
distribution.
Disable
Teamwork
mode
Set the teamwork mode.
The options include
Smart and iCooling.
Determine whether to
enable the iCooling
mode based on onsite
heat load variations. If
the heat load varies
greatly, it is
recommended that you
enable the iCooling
mode. The parameter can
only be modified on the
ECC WebUI and cannot
be modified on the smart
cooling product screen.
Smart
Enable
L1/L2
linkage
Enable or disable L1/L2
linkage.
Set this parameter based
on site requirements. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Disable
Network
Networking mode for the
teamwork. The
networking mode set on
the screen must be
consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode
Networked over CAN or
MAC_CAN.
CAN
indicates teamwork
control over a CAN bus,
MAC_CAN
teamwork
control over an FE port.
MAC_CAN