6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
178
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
humidity
linkage
function of the
iCooling is
disabled.
2.
The cables to
the T/H sensor
of the cabinet
are loose or,
and the L1/L2
humidity
linkage
function of the
iCooling is
disabled.
3.
The aisles T/H
sensor of smart
cooling product
is faulty.
4.
The cables to
the aisles T/H
sensor of the
smart cooling
product are
loose or
damaged.
5.
The DIP switch
of the T/H
sensor is set
incorrectly.
6.
The
communication
port of the
control board is
faulty.
7.
The ETH
converter is
faulty.
8.
The smart
socket is faulty.
cables to the temp sensor,
the rack environment unit,
and the supervisory (ECC).
3.
Maintain or replace the
T/H sensor of smart
cooling product.
4.
Maintain or replace the
cables between the T/H
sensor and the control
board.
5.
Set the DIP switch
correctly for T/H sensor.
6.
Maintain or replace the
control board.
7.
Check the ETH converter
works properly.
8.
Check the rack
environment unit works
properly.
a176
Insufficient
water supply
locked
Major
Stop
humidification
1.
The water
supply pressure
is insufficient.
2.
The water
supply is cut
off, the water
inlet pipe is
blocked, or the
water source
has no water.
3.
The water inlet
solenoid valve
is faulty or
blocked.
4.
The drainage
1.
Verify that the water
supply pressure is 0.1 to
0.7 MPa.
2.
Verify that the water
supply pipe is unblocked,
and the water source has
water.
3.
Verify that cables to the
water inlet solenoid valve
are properly connected.
Wash or replace the valve
if necessary.
4.
Verify that cables to the
drainage solenoid valve are
properly connected. Wash