NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
35
Figure 3-7
External structure (unit: mm)
(1) Connecting kits
(2) Control panel
(3) Door lock
(4) Front door
(5) Fixing port
(6) Side panel
(7) Leveling foot
(8) Rear door
In the figure, D is the depth of the cabinet. It can be 1100 mm or 1200 mm.
3.1.5 Installation Layout Principles
Layout principles for installing the NetCol5000-A are as follows:
If the outdoor unit is placed higher than the indoor unit, the maximum vertical distance
between them is 20 m. To ensure the NetCol5000-A reliability, make an oil trap every 5
m to 6 m along pipes in the vertical direction.
If the indoor unit is placed higher than the outdoor unit, the maximum vertical distance
between them is 5 m.