NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
168
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
cooling product
and the ETH
converter or the
supervisory.
ETH converter or the
supervisory.
a118
Main power off
Major
The alarm is
generated, and
the electric
heater and
humidifier are
shut down.
1.
The main
power supply is
faulty.
2.
The main
power cable is
in poor contact.
1.
Check the main power
supply.
2.
Check the main power
cable.
a119
L1/L2 linkage
condition not
met
Major
The alarm is
generated, and
the L1/L2
linkage
function of the
iCooling is
disabled.
1.
The cables to
the temp sensor
of the cabinet
are loose or
damaged.
2.
The temp
sensor of the
cabinet is
faulty.
3.
The monitoring
host (ECC) is
faulty.
4.
The rack
environment
unit is faulty.
5.
The temp
sensor
configuration of
the supervisory
(ECC) is faulty.
6.
The
configuration of
the smart
cooling product
is faulty.
7.
Teamwork
settings are
incorrect for the
master unit.
1.
Maintain or replace the
cables to the temp sensor,
the rack environment unit,
and the supervisory (ECC).
2.
Maintain or replace the
temp sensor of cabinets.
3.
Check or maintain the
supervisory (ECC).
4.
Check or maintain the rack
environment unit.
5.
Check the configuration
between the temp sensor
and the cabinet is correct.
6.
Check the configuration of
the supervisory (ECC) is
correct.
7.
Set Total number of units
on the master unit to the
actual number of units.
a120
A/C abnormal
L1/L2
disconnect
Major
The alarm is
generated, and
the L1/L2
linkage
function of the
iCooling is
disabled.
1.
Teamwork
settings are
incorrect for
slave units.
2.
Teamwork
settings are
incorrect for the
master unit.
3.
Slave unit is
power off or
1.
Modify teamwork settings
for slave units to enable
slave units to join the
teamwork group.
2.
Set Total number of units
on the master unit to the
actual number of units.
3.
Power on the slave unit.
Check the slave unit
Teamwork Wire
Содержание NetCol5000-A021
Страница 234: ......