NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
148
Item
Method
Troubleshooting
Humidifier
reported.
cylinder.
After the electrode humidifier
starts, choose
Running
>
Device Details
>
Humidifier
on the main screen to make
sure that the current of each
phase is not less than 2.0 A
(conductivity > 100).
Replace the electrode humidifier
cylinder.
Wet film
humidifier
The humidifier float has no
scale, and humidifier float
functions properly.
Clean or replace the humidifier float.
The wet film and humidifier
water pan are clean and have
no scale.
Replace the wet film humidifier. The
wet film should be replaced every 12
months.
No operating overtime alarm
is generated on the wet film
humidifier.
Replace the wet film humidifier.
The upstream water pan filter
of the humidifier pump is not
dirty or blocked.
Remove and clean the water pan filter.
Remove the two screws and sheet metal fastener from the water pan filter and pull out the
filter, as shown in
Figure 6-2
Cleaning the water pan filter
6.2.4 Semiannual Maintenance Items
Before maintaining the electric heater, you need to remove the fan.
Содержание NetCol5000-A021
Страница 234: ......