NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
58
Figure 3-31
Positions of needle valves
(1) Liquid pipe needle
valve
(2) Discharge pipe needle
valve
(3) Low-pressure needle
valve
Procedure
Step 1
Remove the bonnets of the liquid pipe needle valve, low-pressure needle valve, and discharge
pipe need valve in turn, as shown in
You will hear a sound of strong air flow when air is being exhausted.
Step 2
Connect a hose to the liquid pipe needle valve, low-pressure needle valve, and discharge pipe
need valve in turn to slowly exhaust nitrogen.
Step 3
Reinstall the valve bonnets until no air exhausts from the needle valves.
----End