NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
95
Parameter
Description
Configuration Principle
Hot-aisle temp
set point,
Hot-aisle humid
set point
Cold aisle sensor
1, 2, 3
Sets the sensors in
cold aisles to
Enable
.
Enable the corresponding humidity and
temperature sensor installed in the cold aisle.
Hot aisle sensor
1, 2, 3
Sets the sensors in hot
aisles to
Enable
.
Enable the corresponding humidity and
temperature sensor installed in the hot aisle.
----End
4.3.2.3 Setting Communications Parameters (IP Settings)
Procedure
Step 1
On the home screen, choose
Settings
>
Comm Settings
>
IP Settings
displayed.
Figure 4-7
Setting the IP address, subnet mask, and gateway address
Step 2
Set the parameters by referring to
Table 4-3
IP address settings
Parameter
Setting Method
IP assigning
mode
Set according to the actual plan
IP address
Set according to the actual plan
Subnet mask
Set according to the actual plan
Gateway
Set according to the actual plan
----End