NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
68
Figure 3-40
Nitrogen injection and pressure preservation
(1) Nitrogen cylinder
(2) Reducing valve
(3) Low-pressure gauge
(4) High-pressure gauge (5) Discharge pipe needle valve (6) Low-pressure needle valve
Step 2
Inject 3.0 MPa nitrogen and preserve the pressure for 24 hours. The system pressure should
stay constant under unchanging ambient temperature conditions. If there is considerable
temperature change and the pressure changes, perform the test again.
Step 3
If welding defects exist, locate and repair the leaking point. If the pressure does not change,
exhaust the nitrogen through the injection needle valves.
----End