If teamwork succeeds, the teamwork icon is green. If teamwork fails, the teamwork icon is red. If
teamwork mode is disabled, the teamwork icon is gray.
----End
Follow-up Procedure
After you have completed the settings, perform the following checks to confirm whether the
teamwork control is available:
1.
Check whether the device number on the topology is the same as the actual device
number.
−
−
If no, check the cable connection and the settings of teamwork control parameters.
2.
Check whether the number of the active devices on the topology is the same as the actual
device number.
−
−
If no, check the cable connection and the settings of teamwork control parameters.
3.
Check whether the number of standby devices on the topology is the same as the actual
device number.
−
−
If no, check the cable connection and the settings of teamwork control parameters.
4.
Check whether the number of online devices on the topology is the same as the actual
device number.
−
If yes, the check is complete.
−
If no, check the cable connection and the settings of teamwork control parameters.
4.3.2.6 (Optional) Setting Alarm Parameters
Prerequisites
Before setting the alarm parameters, get familiar with the relationship among each parameter.
Configurations of temperature and humidity alarms and main board alarms for the air cooled
devices comply with the following relationships:
Power underfreq alarm threshold < Power overfreq alarm threshold
Supply-air HT alarm thr 5°C ≤ Return-air HT alarm threshold
Supply-air HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm thr 5°C ≤ Return-air HT alarm threshold
Supply-air LT alarm thr 5°C ≤ Return-air LT alarm threshold
Context
The content described in this section is optional. To set whether to report an alarm, or set
the time delay duration or threshold, follow the instructions in this section. The enabling