NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
153
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
HT lock
the compressor
is forcibly shut
down.
alarm is generated
frequently.
alarm.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a015
Comp exceed
runtime
Warning
The alarm is
generated.
The accumulated
runtime of the
comp exceeds the
alarm threshold.
Maintain or replace the comp
and clear the accumulated
runtime.
a018
Indoor fan
1/2/3/4/5/6
exceed runtime
Warning
The alarm is
generated.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
Maintain or replace the indoor
fan and clear the accumulated
runtime.
a023
Elec heater 1
HT
Major
The alarm is
generated, and
the electric
heater is
forcibly shut
down.
1.
The cables to
the temp switch
of the elec
heater are loose
or damaged.
2.
The temp
switch is faulty.
3.
The indoor fans
are faulty.
1.
Check the cables to the
temp switch of the elec
heater.
2.
Replace the elec heater.
3.
Maintain or replace the
indoor fans.
a024
Elec heater 1
exceed runtime
Warning
The alarm is
generated.
The accumulated
runtime of the elec
heater exceeds the
alarm threshold.
Maintain or replace the elec
heater and clear the
accumulated runtime.
a025
Air filter
blocked
Warning
The alarm is
generated, and
the electric
heater and
humidifier are
shut down.
1.
Air filters are
blocked.
2.
The differential
press switch is
faulty.
3.
The differential
press switch is
set
inappropriately.
4.
The pressure
inlet tube of the
differential
pressure switch
is blocked or
disconnected.
5.
The cables to
the differential
press switch are
loose or
damaged.
1.
Maintain or replace the air
filters.
2.
Replace the differential
press switch.
3.
Adjust the threshold of the
differential press switch.
4.
Maintain or replace the
press tube.
5.
Check the cables to the
differential press switch.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a026
Air filter exceed
runtime
Warning
The alarm is
generated.
The accumulated
runtime of air filter
Maintain or replace the air
filter and clear the