NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
162
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
2.
The condenser
fins are
blocked.
3.
The outdoor
units do not run
properly.
4.
The refrigerant
is overfilled.
5.
The comp is
faulty.
3.
Maintain or replace the
outdoor units.
4.
Decrease certain amount of
refrigerant.
5.
Maintain or replace the
comp.
a069
Comp startup
failed
Major
The alarm is
generated.
1.
The comp is in
lack of oil.
2.
The comp
driver is faulty.
3.
The comp is
faulty.
1.
Fill oil to the comp.
2.
Maintain or replace the
comp driver.
3.
Maintain or replace the
comp.
a070
Comp drive fan
fault
Major
The alarm is
generated.
The fans in the
comp driver are
faulty.
Check the fans in the comp
driver.
a071
Comp drive
module
overheat
Major
The alarm is
generated.
1.
The fans in the
comp driver are
faulty.
2.
Dirt exists in
the air vents of
the fans in the
comp driver.
1.
Check the fans in the comp
driver.
2.
Clean the air vents of the
fans in the comp driver.
a072
Comp drive U
phase loss
Major
The alarm is
generated.
1.
The cables to
phase U of the
comp driver are
loose or
damaged.
2.
The comp
driver is faulty.
1.
Check the cables to the
comp driver.
2.
Maintain or replace the
comp driver.
a073
Comp drive V
phase loss
Major
The alarm is
generated.
1.
The cables to
phase V of the
comp driver are
loose or
damaged.
2.
The comp
driver is faulty.
1.
Check the cables to the
comp driver.
2.
Maintain or replace the
comp driver.
a074
Comp drive W
phase loss
Major
The alarm is
generated.
1.
The cables to
phase W of the
comp driver are
loose or
damaged.
2.
The comp
driver is faulty.
1.
Check the cables to the
comp driver.
2.
Maintain or replace the
comp driver.