5 Power-On Commissioning
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
133
Table 5-1
Refrigerant and Refrigerant oil to be charged for NetCol500-A0265S11E0
Item
Length of one-way pipeline (m)
0 < L ≤ 10
10 < L ≤ 80
Refrigerant (kg)
9
9 + (L – 10) x 0.19
Refrigerant oil
(kg)
0
0
If the length of one-way pipeline of NetCol500-A0265S11E0 without low-temperature component is 80
meters, the refrigerant to be charged = 9 + (80 – 10) x 0.19 = 22.3 kg.
5.2.2 (Optional) Charging Refrigerant Oil
Prerequisites
Check whether refrigerant oil needs to be added by referring to
Refrigerant and Refrigerant Oil to Be Charged
. If not, directly vacuumize the cooling
system by referring to
There is no need to charge refrigerant oil upon the initial commissioning.
If you need to charge refrigerant oil onsite during maintenance, see
Context
Ensure that the leather hose connectors are fastened before charging refrigerant oil and
vacuumizing the cooling system.
Procedure
Step 1
Connect the barrel with the pre-weighed refrigerant oil to the low-pressure needle valve
through a leather hose, and connect the vacuum pump to the discharge pipe needle valve, as
shown in