NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
173
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
a138
EEV high
overheating
degree
Major
The alarm is
generated, and
the compressor
is shut down.
1.
The electronic
expansion valve
coil is loose.
2.
The electronic
expansion valve
coil is faulty.
3.
The electronic
expansion valve
is faulty.
1.
Reinstall the electronic
expansion valve coil.
2.
Replace the electronic
expansion valve coil.
3.
Replace the electronic
expansion valve.
a139
EEV high
overheating
locked
Critical
The alarm is
generated, and
the compressor
is shut down.
1.
The electronic
expansion valve
coil is loose.
2.
The electronic
expansion valve
coil is faulty.
3.
The electronic
expansion valve
is faulty.
1.
Reinstall the electronic
expansion valve coil.
2.
Replace the electronic
expansion valve coil.
3.
Replace the electronic
expansion valve.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a140
EEV auto
control fault
Critical
The alarm is
generated, and
the compressor
is shut down.
1.
The suction
pressure sensor
is faulty.
2.
The suction
temperature
sensor is faulty.
1.
Verify that the suction
pressure sensor works
properly.
2.
Verify that the suction
temperature sensor works
properly.
a141
EEV driver
comm. Fault
Major
The alarm is
generated.
1.
The electronic
expansion valve
driver is faulty.
2.
The
communication
port of the
control board is
faulty.
1.
Replace the control board.
2.
Maintain or replace the
control board.
a142
EEV driver
fault
Major
The alarm is
generated.
1.
Cables to the
electronic
expansion valve
coil are not
properly
connected.
2.
The electronic
expansion valve
driver is faulty.
1.
Check cables to the
electronic expansion valve
driver.
2.
Replace the control board.
a143
Outdoor fan
communication
failure
Major
The alarm is
generated.
1.
The indoor and
outdoor
communication
s cable is not
properly
connected.
2.
The outdoor fan
1.
Check the indoor and
outdoor communications
cable.
2.
Maintain or replace the
outdoor fan driver.
3.
Power on the outdoor unit.
4.
Maintain or replace the