NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
179
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
solenoid valve
leaks.
5.
Humidifier
electrodes or
cable
connections are
faulty, and no
current exists in
the cylinder.
6.
The high water
level sensor
circuit is faulty.
7.
The high water
level sensor is
short-circuited.
or replace the valve if
necessary.
5.
Verify that cables to
humidifier electrodes are
properly connected, and
electrodes work properly.
6.
Check the high water
level sensor circuit.
7.
Open the humidifier
cylinder and clean the high
water level sensor.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a177
Humidity
invalid L1/L2
interrupt
Major
The alarm is
generated, and
the L1/L2
linkage
function of the
iCooling is
disabled.
1.
All T/H sensor
of cabinet is
faulty.
2.
All cables to
the T/H sensor
of the cabinet
are loose or
damaged.
3.
All aisles T/H
sensor of smart
cooling product
is faulty.
4.
All cables to
the aisles T/H
sensor of the
smart cooling
product are
loose or
damaged.
5.
All DIP switch
of the T/H
sensor is set
incorrectly.
6.
All
communication
port of the
control board is
faulty.
7.
The ETH
converter is
faulty.
8.
The smart
socket is faulty.
1.
Maintain or replace the
T/H sensor of cabinet.
2.
Maintain or replace the
cables to the temp sensor,
the rack environment unit,
and the supervisory (ECC).
3.
Maintain or replace the
T/H sensor of smart
cooling product.
4.
Maintain or replace the
cables between the T/H
sensor and the control
board.
5.
Set the DIP switch
correctly for T/H sensor.
6.
Maintain or replace the
control board.
7.
Maintain or replace the
ETH converter.
8.
Maintain or replace the
smart socket.
a184
Compressor
preheating
Warning
The alarm is
The compressor
heating belt is
Wait until the preheating is
complete or manually stop