NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
2 Product Description
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
20
Physical Ports
Table 2-4
Physical ports
Item
Specifications
Refrigerant liquid pipe
Copper pipe, with an outer diameter of 5/8 inch (15.88 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding.
Refrigerant gas pipe
Copper pipe, with an outer diameter of 3/4 inch (19.05 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding.
Water inlet pipe to the
humidifier
Reserved: BSPP 1/2 inch reserved copper tube.
Installation Requirements
When the total load of servers, relative to a single smart cooling product, is less than 5 kW,
the humidity might be relatively high. It has no relationship with product quality, and you are
recommended to install a dehumidifier.
Table 2-5
Installation requirements
Item
Specifications
Door
Width: not smaller than 0.9 m; height: not smaller than 2.3 m.
Floor
Bearing capacity not smaller than 350 kg/m
2
; for raised floors,
height not smaller than 250 mm.
Installation mode
Installed on a concrete floor, base, or an ESD floor.
Pipe and cable routing
Cables and pipes can be routed overhead or at the bottom.
Length of one–way
refrigerant pipes
≤ 80 m.
Height difference
between the indoor and
outdoor units
If the outdoor unit is placed higher than the indoor unit, the
maximum vertical distance between them is 20 m.
If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 m.
Thickness of the thermal
insulation foam
≥ 13 mm.
Inner diameter of the
thermal insulation foam
Liquid pipe: 16 mm.
Gas pipe: 19 mm.