NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
36
When calculating the height difference, the compressor base is regarded as the baseline for
the indoor unit.
The inverted trap should be higher than the top copper pipe of the condenser.
In the figure,
is a sign of a tilt, indicating that the scale of the pipe tilting is at least
1:200. The pipe tilting direction should be consistent with the hypotenuse of the right
triangle.
If the indoor unit is placed higher than or equal to the outdoor unit, inverted traps or oil
traps are not needed.
Protective tubes should be installed for wall- and floor-through pipes. The spacing
between the protective tubes and pipes should be filled with fireproof mud
(recommended).
Figure 3-8
Routing pipes from the bottom
(1) Inverted traps
(2) Oil traps
(3) Tilted gas pipe
(4) Tilted liquid pipe