NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
154
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
exceeds the alarm
threshold.
accumulated runtime
a027
Power loss
Warning
The alarm is
generated.
The supply power
is cut off.
Check the power supply
cables.
a028
Power phase A
overvolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too high.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a029
Power phase B
overvolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too high.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a030
Power phase C
overvolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too high.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a031
Power phase A
undervolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too low.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a032
Power phase B
undervolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too low.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a033
Power phase C
undervolt
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply voltage
is too low.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
voltage.
2.
Replace the SPD
three-phase test board.
a034
Power overfreq
Major
The alarm is
generated, and
the system
shuts down.
1.
The power
supply
frequency is too
high.
2.
The SPD
three-phase test
board is faulty.
1.
Check the power supply
frequency.
2.
Replace the SPD
three-phase test board.