NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
104
−
Allow
Alarms are reported to the EMS. Active alarms are displayed on the LCD and the
system performs related protection actions.
−
Block
New alarms are not reported to the EMS. The EMS can detect alarms that are
generated before the blocking. Active alarms are displayed on the LCD and the
system performs related protection actions.
−
Disallow
Alarms are not generated and no protection actions are performed.
The method for setting each alarm is the same. This section describes how to set
Delay
of
Supply-air HT
to
5
.
Be careful when configuring alarms. Only professional maintenance personnel can change
alarm settings.
Procedure
Step 1
Choose
Settings
>
Alarm Settings
>
T/H Sensor
on the home screen.
displayed.
Figure 4-11
Setting alarm parameter 1
Step 2
Tap
Delay
following
Supply-air HT
.
Step 3
Set the value to
5
and tap
, as shown in