NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
100
Parameter Description
Configuration
Principle
Default Value
humidity control type
and set points of the
master device and
other parameters) to
the slave device, and
all the smart cooling
products in the group
refer to the mode
delivered by the
master device.
When the requirement
control is
Disable
, the
master device does
not synchronize data
to the slave device,
and all the smart
cooling products
operate based on their
own requirements,
not referring to the
mode delivered by the
master device.
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
Cascade
After the requirement
control is enabled, you
can configure Cascade.
The cascade function
starts standby smart
cooling products if the
active one cannot meet
the refrigerating
requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Large ring
cooling
capacity P
Proportion coefficient in
L1/L2 linkage PID
control.
You are not
recommended to change
the value.
0.10
Large ring
cooling
capacity I
Integration coefficient in
L1/L2 linkage PID
control.
You are not
recommended to change
the value.
350s
Large ring
cooling
capacity D
Differential coefficient in
L1/L2 linkage PID
control.
You are not
recommended to change
the value.
10s
Cooling
capacity
adjustment
period
Adjustment period in
L1/L2 linkage PID
control.
You are not
recommended to change
the value.
5s
L1/L2
linkage
cooling stop
Reference temperature at
which the smart cooling
product stops cooling in
the cooling mode in
Set this parameter based
on the lowest
temperature allowed
onsite. Normally you are
18.0°C