NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
172
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
Manual clear
on the alarm page.
a131
Drainage
solenoid fault
Major
The humidifier
is shut down.
The drainage
solenoid valve is
faulty.
Replace the drainage solenoid
valve.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a132
Cylinder
maintenance
due
Warning
The alarm is
generated.
The scheduled
humidifier cylinder
maintenance time
is reached.
Clean the humidifier
cylinder.
a133
Cylinder
replacement
due
Major
The humidifier
is shut down.
The running time
of the humidifier
cylinder has
reached the set
threshold.
Replace the humidifier
cylinder.
a134
Suction temp
sensor fault
Major
The alarm is
generated.
1.
Cables to the
temperature
sensor are not
properly
connected.
2.
The
temperature
sensor is faulty.
1.
Check cables to the
temperature sensor.
2.
Maintain or replace the
temperature sensor.
a136
EEV low
overheating
degree
Major
The alarm is
generated, and
the compressor
is shut down.
1.
The electronic
expansion valve
coil is loose.
2.
The electronic
expansion valve
coil is faulty.
3.
The electronic
expansion valve
is faulty.
4.
The dehumid
solenoid valve
coil is faulty.
1.
Reinstall the electronic
expansion valve coil.
2.
Replace the electronic
expansion valve coil.
3.
Replace the electronic
expansion valve.
4.
Maintain or replace
dehumid solenoid valve
coil.
a137
EEV low
overheating
locked
Critical
The alarm is
generated, and
the compressor
is shut down.
1.
The electronic
expansion valve
coil is loose.
2.
The electronic
expansion valve
coil is faulty.
3.
The electronic
expansion valve
is faulty.
4.
The dehumid
solenoid valve
coil is faulty.
1.
Reinstall the electronic
expansion valve coil.
2.
Replace the electronic
expansion valve coil.
3.
Replace the electronic
expansion valve.
4.
Maintain or replace
dehumid solenoid valve
coil.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.