Model Kühl and Kühl + Series 

 

 

 

 

Installation Instructions  

Temperature Sensor Kit 

For Use with Kühl, Kühl+ units 

Please read these instructions completely before attempting installation. 
NOTE:  These instructions apply to the Friedrich Kühl and Kühl+ units.  
 

  

Kit Contents: 

 

 

 

 

            Quantity 

 

Sensor, Outdoor Air Temperature (Black) 

Sensor, Indoor Return Air Temperature (White) 

Sensor, Indoor Supply Air Temperature (Red) 

Sensor, Indoor Coil Temperature (Green) 

Sensor, Outdoor Coil Temperature (Blue) 

Clip 3/8” OD Tube SS  

Clip 5/16” OD Tube SS 

Tape Cork Insulating 2”x4” roll 

Wire Ties 

Instruction Sheet (2 pg) 

 
Tools Required:  ¼” nut driver, wire cutter snips 
 
Note: Disconnect unit supply cord from the power supply prior servicing the control circuits. 
 

 
Step 1.    Remove existing sensors making note of each sensors location, routing, clip orientation, 

any wire ties used for strain relief, its connector color and its connection point on the 
electronic control. 

 

 
Step 2.    Two sizes of sensor mounting clips are provided for remounting the coil sensors.  The clips 

with a “3” stamped on its side are for 3/8” OD tube coils and the unmarked clip is for 0.312 
OD tubed coils.  Install the new sensor/clips in the same orientation and position as the 
original factory setting.   

 

 
Step 3.   Cut the supplied piece of cork insulating tape into 2 equal size pieces (2” x 2”).  Place one 

piece over each mounted coil sensor.  The purpose of the tape is to insulate the sensor 
from outside influences and to secure the sensor/clip to the coil return bend.   

 
Step 4.     Route the sensor leads’ to the units’ control box and secure the leads with wireties for 

strain relief. Cut excess wire tie with wire snips.

 

 