Troubleshooting
Table 5-2: Is the System Power LED Off?
Answer Possible
Reasons Possible
Solutions
The system is not connected to
AC power, or no AC power is
available.
Be sure that the power cord is
connected to the power supply.
Check the power distribution
unit, UPS, or AC circuit.
A power supply problem exists.
The power supply may not be
connected or inserted properly, it
may have a damaged connector,
or it may have failed.
Be sure that the power supply is
undamaged, the power supply is
fully seated, and the power
supply LED is illuminated green
when you power up the server.
A broken connection exists
between the front panel LED
assembly and the power
backplane.
Be sure that the system power
and power supply signal cables
are connected to the system
board and power backplane.
Yes, it is off
The front panel LED assembly has
failed.
Be sure that the front panel LED
assembly cable is connected to
the power backplane.
Refer to the
HP Servers
Troubleshooting Guide
for
further options.
No
If the system power button LED is illuminated amber, do the following:
1. Press the Power On/Standby button.
2. Refer to Table 5-3.
Note:
For LED locations and functions, refer to Chapter 4, “Connectors, LEDs, and Switches.” For
cabling configurations, refer to the
HP ProLiant ML570 Generation 2 Server Setup and Installation
Guide
.
5-4
HP ProLiant ML570 Generation 2 Server Maintenance and Service Guide