Specification
Value
Power supply output
Rated steady-state power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power
800 W at 200 VAC to 277 VAC input
800 W at 380 VDC input
WARNING:
To reduce the risk of electric shock or energy hazards:
• This equipment must be installed by trained service personnel, as defined by the NEC and IEC
60950-1, Second Edition, the standard for Safety of Information Technology Equipment.
• Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no
direct connection to a primary circuit and derives its power from a transformer, converter, or
equivalent isolation device.
• The branch circuit overcurrent protection must be rated 27 A.
CAUTION:
This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to
the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
• This equipment must be connected directly to the DC supply system earthing electrode conductor or
to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing
electrode conductor is connected.
• This equipment must be located in the same immediate area (such as adjacent cabinets) as any
other equipment that has a connection between the earthed conductor of the same DC supply circuit
and the earthing conductor, and also the point of earthing of the DC system. The DC system must be
earthed elsewhere.
• The DC supply source is to be located within the same premises as the equipment.
• Switching or disconnecting devices must not be in the earthed circuit conductor between the DC
source and the point of connection of the earthing electrode conductor.
HPE 1600W Flex Slot Platinum Hot Plug Low Halogen Power Supply
Specification
Value
Input requirements
Rated input voltage
200 VAC to 240 VAC
240 VDC for China only
Rated input frequency
50 Hz to 60 Hz
Rated input current
8.7 A at 200 VAC
7.2 A at 240 VAC
Table Continued
HPE 1600W Flex Slot Platinum Hot Plug Low Halogen Power Supply
137