7.6
Thermal Problems and Environmental Status
Overtemperature conditions can cause the system to shut down.
The
AlphaServer
TS15 system operates within an ambient temperature range of 5ºC to 40ºC
(41
°
F to 104
°
F). An internal sensor monitors the system temperature and shuts down the
system if maximum limits are exceeded. If the system shuts down unexpectedly:
•
Ensure that the side cover (pedestal) or top cover (rack) are properly secured.
•
Verify that the ambient temperature does not exceed the specified limits.
•
Make sure there are no obstructions to the airflow at the front or rear of the system.
•
Check to see that the cables inside the system are properly dressed. A dangling cable
can impede airflow to the system.
Troubleshooting with show power Command
The SRM console
show power
command can help you determine if environmental
problems necessitate the replacement of a power supply, system fan or fans, or the
motherboard.
Show power indicates:
Action
Bad voltage
Replace the power supply and or the system motherboard.
Contact HP Services.
Bad fan
Replace the indicated fan or fans. Contact HP Services.
Bad temperature
The problem could be a bad fan (fans) or an obstruction
to the airflow. Check the airflow first. If there is no
obstruction, contact HP Services to replace the bad fan.
7-8
hp AlphaServer TS15 Owner's Guide
Содержание AlphaServer TS15
Страница 6: ......
Страница 34: ...Figure 1 14 VGA Monitor Connected to Optional Video Card B 1 2 A MR0647 1 18 hp AlphaServer TS15 Owner s Guide ...
Страница 91: ...Figure 4 3 Removing the Top Cover A 2 1 4 5 3 MR0642 Installing and Configuring Options 4 5 ...
Страница 188: ...Figure 6 4 Setup for RMC with VGA Monitor A 1 2 B MR0626 ENET VGA 6 10 hp AlphaServer TS15 Owner s Guide ...
Страница 213: ...Figure 6 5 RMC Jumpers Default Positions Using the Remote Management Console 6 35 ...
Страница 252: ......