HVAC A
PPLICATION
Honeywell
• 36
3.5.5
Group 3.3: Control reference settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.3.1
Minimum frequency
0.00
M3.3.2
Hz
0.00
101
Minimum allowed frequency
reference
M3.3.2
Maximum frequency
M3.3.1
320.00
Hz
60.00
102
Maximum allowed frequency
reference
M3.3.3
I/O control reference A
selection
1
8
6
117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
M3.3.4
I/O control reference B
selection
1
8
4
131
Selection of ref source when
control place is I/O B. See
above.
NOTE
: I/O B control place
can only be forced active
with digital input (M3.5.1.5).
M3.3.5
Keypad Ctrl Refer-
ence selection
1
8
2
121
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
M3.3.6
Keypad reference
0.00
M3.3.2
Hz
0.00
184
The frequency reference can
be adjusted on the keypad
with this parameter.
M3.3.7
Keypad direction
0
1
0
123
Motor rotation when control
place is keypad
0 = Forward
1 = Reverse
M3.3.8
Keypad reference
copy
0
2
1
181
Selects function for Run state
& Reference copy when
changing to Keypad control:
0 = Copy reference
1 = Copy ref & Run State
2 = No copying
M3.3.9
Fieldbus control refer-
ence selection
1
8
3
122
Selection of ref source when
control place is Fieldbus:
1 = Preset frequency 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer